Specifications of Optional Functions

Specifications of Optional Functions
/A1, /A2, /A3, /A4, /A5 Alarm Output Relays Number or output Select from 2, 4, 6, 12* and 24* points
* Only for DX2000
/C2, /C3 Serial Communication Interface Connection EIA RS-232 (/C2) or RS-422A/485 (/C3)
Protocols DX private protocol, Modbus(master/slave) protocol
Setting/measurement server function Operation, setting or output of measurement data are available by DX private protocol.
Modbus communication Reading or writing of measurement data on other instruments are available by Modbus protocol.*
* /M1 option or /MC1 option is required to read data from other instrument.
/D5 VGA Video Output Resolution 640 x 480 pixels (VGA)
/F1 Fail/Status Output The relay contact output on the rear panel indicates the occurrence of CPU failure or selected status.
/F2 (only for DX2000) Fail & Alarm Output Relays 22 points Combination of "Fail/Status output function" and "Alarm output relays 22 points".
/H2 Clamped Input Terminal Clamped input terminal (detachable type) is used for input terminal.
/H5[ ], /H5* Desk Top Type Provides carrying handle and power cord.
* /H5 is only for 24 VDC/AC power supply model (/P1), and does not include power code.
/M1 Mathematical Functions Channel assignable to calculated data DX1000 DX1002, DX1004: 12 channels
DX1006, DX1012: 24 channels
DX2000 DX2004, DX2008: 12 channels
DX2010, DX2020, DX2030, DX2040, DX2048: 60 channels
Constant Up to 60 constants (K01 to K60)
Report type Hourly, daily, hourly + daily, daily +weekly and daily + monthly
Types of mathematical reports Max. 4 types are selectable from average, maximum, minimum, instantaneous and summation
/N1 Cu10, Cu25 RTD Input /3 Leg Isolated RTD Input This option allows Cu10 and Cu25 inputs to be added to the standard input types.
/N2* 3 Legs Isolated RTD Input A, B, b legs are of isolated input type.
* Only for DX1006, DX1012, DX2010, DX2020, DX2030, DX2040 and DX2048.
/N3 Extended Input Types TC Kp vs Au7Fe, PLATINEL, PR40-20, NiNiMo, W/Wre26, TypeN (AWG14)
RTD Pt25, Pt50, Ni100 (SAMA), Ni100 (DIN), Ni120, J263*B, Cu53, Cu100
/P1 24 VDC/AC Power Supply Rated power supply 24 VDC or 24 VAC (50/60 Hz)
Allowable power supply voltage range 21.6 to 26.4 VDC/AC
Max. power consumption DX1000 28 VA (24 VDC), 45 VA (24 VAC (50/60 Hz))
DX2000 45 VA (24 VDC), 70 VA (24 VAC (50/60 Hz))
/R1 Remote Control This option allows eight functions to be controlled remotely by a contact input.
/TPS2*, /TPS4, /TPS8* 24 VDC Transmitter Power Supply /TP2: 2 loops, /TPS4: 4 loops, /TPS8: 8 loops
* /TPS2 is only for DX1000, /TPS8 is only for DX2000
Output voltage 22.8 to 25.2 VDC (rated load current)
Rated output current 4 to 20 mADC
/KB1, /KB2 Easy Text Entry   Remote control terminal is available to operate the DX.
Number of units that can be controlled Max. 32 units by ID setting
/USB1 USB Interface USB interface specification Based on Rev1.1, host function
Number of ports 2 ports (Front and rear panel))
Available USB devices Keyboard 104/89 keyboard (US) based on USB HID Class Ver.1.1
External medium USB flash drive (Some of the USB flash drive may not be supported by DXAdvanced.)
/PM1 Pulse Input Pulse input option includes mathematical functions option (/M1) and remote control option
Number of inputs 3 points (8 points are available in case of using remote inputs)
Input format Photocoupler isolation (shared common) Isolated power supply for input terminal (approx. 5 V)
/CC1 Calibration Correction Function Corrects the measurement value of each channel using segment linearizer approximation.
Number of segment points 2 to 16
/MC1 (only for DX2000) External Input Function Digital input channels via communication are extended to input data from other instruments.
Number of external input channels Up to 240 channels (channel number: 201 to 440)
* Only for DX2010, DX2020, DX2030, DX2040 and DX2048
* Fast sampling mode is not available when external input option is equipped.
/BT2 Multi-batch Function User can start/stop recording independently by batch, and create data files.
Number of multi-batches DX1000 2 to 6
(Only for DX1006, DX1212)
DX2000 2 to 12
(Only for DX2010,DX2020,DX2030,DX2040,DX2048)
/CP1 PROFIBUS-DP Communication Interface Function PROFIBUS-DP master devices can access the following internal data.
Write communication input channel data DX1000: Max. 24 channels
DX2000: Max. 32 channels
Node address setting range 0 to 125
Interface PROFIBUS-DP-V0 Slave
Transmission medium 2 dedicated cables
Transmission speed/distance 9.6 kbps/1200 m to 12 Mbps/100 m
Termination resistance None (requires external termination resistance)
/AS1 Advanced security functions (Part 11 compliant) Data anti-tamper function Settings and measured data are saved as encrypted binary files.
Data type Only for display or event
Event data is not possible in Trigger mode
Login function Using the login function described below, you can enter security settings on the instrument
  • User name
  • Password
  • User ID(depend on setting)
User level and number of users System administrator: 5 users (all can be operated)
  • General user: 90 users(With user restrictions, you can set restrictions on performing operations and sign authority.)
  • User restrictions setting: 10 kinds (for general users)
Password expiration time Select form Off, 1month, 3 month, 6month
Password control function Logins are verified by a Kerberos authentication server* (only user name and password)
*The function has confirmed compatibility with Windows Server2003/Windows Server2008 Active Directory
Encryption method AES128-CTS-HMAC-SHA1-96
AES256-CTS-HMAC-SHA1-96
ARCFOUR-HMAC-MD5
Pre-Auth function use
Signature function After checking data that has finished being recorded, you can add three levels of electronic signature, select a path/file, and enter comments (32 characters maximum)
Audit trail function Save operation logs, setting change logs, and their setting file
Discrete alarm ACK function Alarm display and relay output can be cancelled on individual alarms ACK can be performed in the overview display
Extended alarm delay time Alarm delay times of up to 24 hours can be set